BrightFarms Chicago Project
June 2016
Customer : | Brightfams Inc. (Hydronov) |
---|---|
Location : | Rochelle, IL |
Website : | www.brightfarms.com |
Product : | Supply Produce to Giant Food Stores |
Objective : | To provide an engineered chiller package for a hydroponic temp control
Application with a 40°F – 95°F indoor ambient control range. Chilling Load = 90 tons |
Description : | Provided (1) 90 tons refrigerant and (10) 316 SS grid coil heat exchanger properly sized to exchange (chiller) 8 ton load per pool pending heating or chilling operational mode. (2) Pumps properly sized for recirculating chiller with buffer tanks, properly sized for loading, 460V/60Hz motors. (1) 400 gallon buffer tank, (1) Air control package preplumbed to include properly sized expansion tanks, Fill-PRV, and air vents. (12) HEX zone pump packages each pump, check valve and digital temperature controller. (1) Delta preplumbed equipment skids; (1) preplumbed buffer tank & chiller pump skid. Skids fabrication includes; FRP deck & structural FRP “I” beam, Type “L” copper pipe, BFV and Ball Valves, CPVC SC80 Pipe, Pump Disconnects, and Leak Testing. |
Engineered By : | Rick Murray Delta Hydronics rickm@deltahydro.com 727-861-2421 |